HDW-675 T5

 

HDW-675 T5

680 kVA Generator set Open Skid

Powered by: DOOSAN
Alternator: MECC ALTE

 

Three phase | 50 Hz | Diesel |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Output: 580kW prp ; 640kW standby
  • Manufacturer: DOOSAN
  • Model: DP222LBF
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 12 - V
  • Bore and Stroke: 128 x 142 mm
  • Displacement: 21,927 L
  • Cooling System: Coolant
  • Lube Oil Specifications: API CH4 SAE 15W40 or 10W40
  • Compression Ratio: 15:1
  • Fuel Consumption ESP: 162,7 l/h
  • Fuel Consumption 100% PRP: 147,1 l/h
  • Fuel Consumption 75 % PRP: 109,2 l/h
  • Fuel Consumption 50 % PRP: 73 l/h
  • Fuel Consumption 25 % PRP: 39,2 l/h
  • Lube oil consumption with full load: 0,5 % of fuel consumption
  • Total oil capacity: 40 L
  • Total coolant capacity: 114 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 24V electrical system
  • Water separator filter (no visible level)
  • Dry air filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Radiator water level sensor (Optional)
  • Self-excited and self-regulated
  • IP23 protection
  • H class insulation
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • 4-pole thermal magnetic circuit breaker
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Battery Switch (Optional)
  • Emergency stop button
  • Steel chassis
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • Generator
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-1 14"
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - Electrical system.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • 4-pole thermal magnetic circuit breaker
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Battery Switch (Optional)
  • - Open set version.
  • Emergency stop button
  • Steel chassis
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 481 ºC
  • Exhaust Gas Flow: 101 m3/min
  • Maximum allowed back pressure: 5,9 kPa
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 2532 m3/h
  • Cooling Air Flow: 14,33 m3/s
  • Alternator fan air flow: 0,9 m3/s
  • - STARTING SYSTEM.
  • Starting power: 7 kW
  • Starting power: 9,52 CV
  • Recommended battery: 200 x 2 Ah
  • Auxiliary Voltage: 24 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Maximum power suction pump: 225 mm Hg
  • Maximum return feed pump: 450 mm Hg
  • Fuel Tank: 875 L
  • - Dimensions.
  • Length: 4.200 mm
  • Height: 2.094 mm
  • Width: 1.600 mm
  • Maximum shipping volume: 14,07 m3
  • Weight with liquids in radiator and sump: 4.494 kg
  • Fuel tank capacity: 875 L
  • Autonomy: 8 Hours
Engine
Oil sump extraction kit 70
Electrical Equipment
Battery Isolator
Water jacket heater D750
Radiator water level sender
Fuel Feeding System
Manual fuel transfer pump
Decanter filter D700S550M515
Decanter filter D700S550M515 - With alarm
Electric fuel transfer pump SC / M6
Electric fuel transfer pump
Residential Silencer
Residential Silencer P475N640K670D750
Protections
Earth Leakage Protection to 630A from 800A to 3200A
CEx Optionals
Telesignal
Kit CAN / LAN
Change over power source unit AC5 / CC2
Repetitive display: Remote Screen
Alarm Indicator Panel RAM7
Kit CAN/RS-485
Kit CAN/USB
Kit MODBUS TCP/IP
Kit CAN Profibus
Kit CAN/SNMP
Fleet Manager Module - C2CLOUD
C2CLOUD - 3G/GRPS and GPS
Kit CAN/LAN HG
Deepsea Optionals
DSE2133: RTD/THERMOCOUPLE Input Expansion Module
DSE2130:Input Expansion Module
DSE2157:Output Expansion Module
DSE2548:Led Output Expansion Module
DSE2152: Analog Outputs Module
DSE2131:Digital / Resistive inputs module
DSE890
Thermal Magnetic Protection
Change from 4P to 3P for 1000A
Change from 4P to 3P for 2000A
Extra to change to motorized circuit breaker 1000A
Extra to change to motorized circuit breaker 2000A
Deepsea
Change of CEx for DSE7310
Change of CEx for DSE7320 controller

Power


kVA

680
 
735
Prime power  (199 - 863)
Stand by  (220 - 949)

kW

544
 
588
Prime power  (159 - 691)
Stand by  (176 - 759)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
420
Width (B)
160
High (C)
209,40
 

Weight


 
Weight
Weight with liquid in radiator and carter

4.494
 

Fuel capacity


 
 
875