HMW-1145 T5

 

HMW-1145 T5

1144 kVA Generator set Soundproof

Powered by: MTU
Alternator: MECC ALTE

 

Three phase | 50 Hz | Diesel |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Output: 956,6kW prp ; 1056,6kW standby
  • Manufacturer: MTU
  • Model: 16V2000G36F
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 16-V
  • Bore and Stroke: 135 x 156 mm
  • Displacement: 35,7 L
  • Cooling System: Water
  • Lube Oil Specifications: ACEA E4, E6, E7, E9
  • Compression Ratio: 17,5
  • Fuel Consumption ESP: 246,86 l/h
  • Fuel Consumption 100% PRP: 223,26 l/h
  • Fuel Consumption 75 % PRP: 167,44 l/h
  • Fuel Consumption 50 % PRP: 115,70 l/h
  • Fuel Consumption 25 % PRP: 63,66 l/h
  • Lube oil consumption with full load: 0,8 % of fuel consumption
  • Total oil capacity including tubes, filters 114 L
  • Total coolant capacity: 150 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Low coolant level sensor
  • Exhaust gas compensator
  • Electronic management (ADEC)
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 24V electrical system
  • Standard air filter
  • Standard fuel filter
  • Standard oil filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Hot parts protection
  • Moving parts protection
  • Self-excited and self-regulated
  • 4 poles
  • AVR governor
  • IP23 protection
  • H class insulation
  • Soundproofing provided by high-density volcanic rock wool
  • High mechanical resistance
  • Low level of noise emissions
  • Door with window to visualize control panel, alarms and measurements
  • Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
  • Residential steel silencer with -35dB attenuation and tilting cap in the exhaust
  • Fuel tank integrated in the chassis
  • Anti-vibration shock absorbers
  • Steel chassis
  • Robust construction designed for continuous or emergency applications
  • Stainless steel fittings
  • Emergency stops
  • Easy access to the power connection
  • Reinforced chassis for heavy range
  • Easy access for chassis cleaning
  • Silent-block with anti-corrosion protection between the genset and the chassis
  • Easy access to fill radiator through the roof
  • Manual oil extraction pump
  • Control panel and emergency stop button
  • Power panel
  • Battery charger (standard on automatic control panels)
  • Water Jacket Heater with single phase pump
  • Battery charge alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • 4 pole circuit breaker
  • Power panel with safety protection in output terminals box (open thermal magnetic protection and alarm)
  • Maintenance-free and anti-explosion battery
  • Battery isolator
  • Generator
  • Poles: 4
  • Connection type (standard): Star - Parallel
  • Mounting type: S-0 18''
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - Container version.
  • Soundproofing provided by high-density volcanic rock wool
  • High mechanical resistance
  • Low level of noise emissions
  • Door with window to visualize control panel, alarms and measurements
  • Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
  • Residential steel silencer with -35dB attenuation and tilting cap in the exhaust
  • Fuel tank integrated in the chassis
  • Anti-vibration shock absorbers
  • Steel chassis
  • Manual oil extraction pump
  • Robust construction designed for continuous or emergency applications
  • Stainless steel fittings
  • Emergency stops
  • Easy access to the power connection
  • Reinforced chassis for heavy range
  • Easy access for chassis cleaning
  • Silent-block with anti-corrosion protection between the genset and the chassis
  • Easy access to fill radiator through the roof
  • - Electrical System Container.
  • Control panel and emergency stop button
  • Power panel
  • Battery charger (standard on automatic control panels)
  • Water Jacket Heater with single phase pump
  • Battery charge alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • 4 pole circuit breaker
  • Power panel with safety protection in output terminals box (open thermal magnetic protection and alarm)
  • Maintenance-free and anti-explosion battery
  • Battery isolator
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 545 ºC
  • Exhaust Gas Flow: 207 m3/min
  • Maximum allowed back pressure: 50 mbar
  • Exhaust Flange Size (external diameter): 200 mm
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 4572 m3/h
  • Cooling Air Flow: 24,37 m3/s
  • Alternator fan air flow: 1,5 m3/s
  • - STARTING SYSTEM.
  • Starting power: 7,5 kW
  • Starting power: 10,2 CV
  • Recommended battery: 200 Ah
  • Auxiliary Voltage: 24 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Fuel Tank: 999 L
  • - Dimensions.
  • Length: 6.058 mm
  • Height: 2.591 mm
  • Width: 2.438 mm
  • Maximum shipping volume: 38,27 m3
  • Weight with liquids in radiator and sump: 12.420 kg
  • Fuel tank capacity: 999 L
  • Autonomy: 6 Hours
  • Sound pressure level: 85 dB(A)@7m
Engine
Oil sump extraction kit 70
Electrical Equipment
Water Jacket heater M1270
Fuel Feeding System
Manual fuel transfer pump
Electric fuel transfer pump SC / M6
Electric fuel transfer pump
Socket Boxes
CBR25 M5 Socket boxes
CBR25 AS5 Socket boxes
Protections
Earth Leakage Protection to 630A from 800A to 3200A
CEx Optionals
Telesignal
Kit CAN / LAN
Change over power source unit AC5 / CC2
Repetitive display: Remote Screen
Alarm Indicator Panel RAM7
Kit CAN/RS-485
Kit CAN/USB
Kit MODBUS TCP/IP
Kit CAN Profibus
Kit CAN/SNMP
Fleet Manager Module - C2CLOUD
C2CLOUD - 3G/GRPS and GPS
Kit CAN/LAN HG
Deepsea Optionals
DSE2133: RTD/THERMOCOUPLE Input Expansion Module
DSE2130:Input Expansion Module
DSE2157:Output Expansion Module
DSE2548:Led Output Expansion Module
DSE2152: Analog Outputs Module
DSE2131:Digital / Resistive inputs module
DSE890
Thermal Magnetic Protection
Change from 4P to 3P for 2000A
Change from 4P to 3P for 3200A
Extra to change to motorized circuit breaker 2000A
Extra to change to motorized circuit breaker 3200A
Deepsea
Change of CEx for DSE7310
Change of CEx for DSE7320 controller

Power


kVA

1144
 
1231
Prime power  (457 - 2572)
Stand by  (504 - 2809)

kW

916
 
984
Prime power  (365 - 2058)
Stand by  (403 - 2247)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
605,80
Width (B)
243,80
High (C)
259,10
 

Weight


 
Weight
Weight with liquid in radiator and carter

12.420
 

Fuel capacity


 
 
999