HFW-440 T6

 

HFW-440 T6

497 kVA Generator set Open Skid

Powered by: FPT_IVECO
Alternator: STAMFORD

 

Three phase | 60 Hz | Diesel |

 

 

  • Engine Specifications 1.800 r.p.m.
  • Rated Output: 425,3kW prp ; 471,3kW standby
  • Manufacturer: FPT_IVECO
  • Model: C13TE7
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct, common rail
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 16 - V
  • Bore and Stroke: 135 x 150 mm
  • Displacement: 12,88 L
  • Cooling System: Liquid (water + 50% glycol)
  • Lube Oil Specifications: ACEA E3 - E5
  • Compression Ratio: 16,5:1
  • Fuel Consumption ESP: 123,3 l/h
  • Fuel Consumption 100% PRP: 110,9 l/h
  • Fuel Consumption 80 % PRP: 87,7 l/h
  • Fuel Consumption 50 % PRP: 57 l/h
  • Total oil capacity including tubes, filters 32 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Inner diameter exhaust pipe: 108 mm
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 24V electrical system
  • Water separator filter (no visible level)
  • Dry air filter
  • Radiator with pusher fan
  • Radiator water level sensor
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • - GENERATOR.
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-1 14"
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Oil sump extraction kit
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • 3-pole thermal magnetic circuit breaker
  • Battery Switch
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 510 ºC
  • Maximum allowed back pressure: 50 mbar
  • Heat dissipated by exhaust pipe: 604 KCal/Kwh
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 1860 m3/h
  • Cooling Air Flow: 13,5 m3/s
  • Alternator fan air flow: 0,92 m3/s
  • - STARTING SYSTEM.
  • Starting power: 7,8 kW
  • Starting power: 10,61 CV
  • Recommended battery: 180 x 2 Ah
  • Auxiliary Voltage: 24 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Fuel Tank: 597 L
  • - DIMENSIONS.
  • Length: 3.310 mm
  • Height: 1.783 mm
  • Width: 1.390 mm
  • Maximum shipping volume: 8,2 m3
  • Weight with liquids in radiator and sump: 3.072 kg
  • Fuel tank capacity: 597 L
  • Autonomy: 7 Hours
Electrical Equipment
Water jacket heater F490
Fuel Feeding System
Water separator filter F400DS300
Water separator filter F400DS300 - With alarm
Electric fuel transfer pump SC / M6
Electric fuel transfer pump
Protections
Earth Leakage Protection to 630A
Earth Leakage Protection to 630A from 800A to 3200A
CEx Optionals
Telesignal
Kit CAN / LAN
Change over power source unit AC5 / CC2
Repetitive display: Remote Screen
Alarm Indicator Panel RAM7
Kit CAN/RS-485
Kit MODBUS TCP/IP
Kit CAN Profibus
Kit CAN/SNMP
Fleet Manager Module - C2CLOUD
C2CLOUD - 3G/GRPS and GPS
Kit CAN/LAN HG
Deepsea Options
DSE2133: RTD/THERMOCOUPLE Input Expansion Module
DSE2130:Input Expansion Module
DSE2157:Output Expansion Module
DSE2548:Led Output Expansion Module
DSE2152: Analog Outputs Module
DSE2131:Digital / Resistive inputs module
DSE890
CC2
CC2 630A
CC2 800A
CC2 1600A
Thermal Magnetic Protection
Change from 3P to 4P for 630A
Change from 3P to 4P for 800A
Change from 3P to 4P for 1600A
Extra to change to motorized circuit breaker 630A
Extra to change to motorized circuit breaker 800A
Extra to change to motorized circuit breaker 1600A
Deepsea
Change of CEx for DSE7310
Change of CEx for DSE7320 controller

Power


kVA

497
 
548
Prime power  (26 - 625)
Stand by  (29 - 690)

kW

398
 
438
Prime power  (24 - 500)
Stand by  (26 - 552)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
331
Width (B)
139
High (C)
178,30
 

Weight


 
Weight
Weight with liquid in radiator and carter

3.072
 

Fuel capacity


 
 
597