HBW-105 T6

 

HBW-105 T6

120 kVA Generator set Open Skid

Powered by: BAUDOUIN
Alternator: MECC ALTE

 

Three phase | 60 Hz | Diesel |

 

 

  • Engine Specifications 1.800 r.p.m.
  • Rated Output: 105,8kW prp ; 115,8kW standby
  • Manufacturer: BAUDOUIN
  • Model: 4M11G106.6
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Bore and Stroke: 105 x 130 mm
  • Displacement: 4,5 L
  • Cooling System: Liquid (water + 50% glycol)
  • Lube Oil Specifications: API CF4, SAE 15W40
  • Compression Ratio: 18:1
  • Fuel Consumption ESP: 28,1 l/h
  • Fuel Consumption 100% PRP: 25,6 l/h
  • Fuel Consumption 75 % PRP: 19,2 l/h
  • Fuel Consumption 50 % PRP: 13,2 l/h
  • Fuel Consumption 25 % PRP: 7,5 l/h
  • Lube oil consumption with full load: 0,2 % of fuel consumption
  • Total oil capacity including tubes, filters 13 L
  • Total coolant capacity: 13,3 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Inner diameter exhaust pipe: 65 mm
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 12V electrical system
  • 24V electrical system
  • Water separator filter (no visible level)
  • Dry air filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Radiator water level sensor
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Self-excited and self-regulated
  • 4 poles
  • AVR governor
  • IP23 protection
  • H class insulation
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Battery Switch
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • 3-pole thermal magnetic circuit breaker
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Steel chassis
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (opcional)
  • Steel residential silencer -35db(A) attenuation. (opcional)
  • Generator
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-3 11"1/2
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - Electrical system.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Battery Switch
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • 3-pole thermal magnetic circuit breaker
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - Open set version.
  • Steel chassis
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump Optional
  • Steel residential silencer -35db(A) attenuation. Optional
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 550 ºC
  • Exhaust Gas Flow: 22,26 m3/min
  • Maximum allowed back pressure: 60 mbar
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 504 m3/h
  • Cooling Air Flow: 3,105 m3/s
  • Alternator fan air flow: 0,573 m3/s
  • - STARTING SYSTEM.
  • Starting power: 4 kW
  • Starting power: 5,44 CV
  • Auxiliary Voltage: 12 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Maximum power suction pump: 375 mm Hg
  • Maximum return feed pump: 375 mm Hg
  • Fuel Tank: 250 L
  • - Dimensions.
  • Length: 2.900 mm
  • Width: 900 mm
  • Weight with liquids in radiator and sump: 1.314 kg
  • Fuel tank capacity: 250 L
  • Autonomy: 13 Hours
Fuel Feeding System
Manual fuel transfer pump
Electric fuel transfer pump SC / M6
Electric fuel transfer pump
CEx Optionals
Telesignal
Kit CAN / LAN
Change over power source unit AC5 / CC2
Repetitive display: Remote Screen
Alarm Indicator Panel RAM7
Kit CAN/RS-485
Kit CAN/USB
Kit MODBUS TCP/IP
Kit CAN Profibus
Kit CAN/SNMP
Fleet Manager Module - C2CLOUD
C2CLOUD - 3G/GRPS and GPS
Kit CAN/LAN HG
CC2
CC2 125A
CC2 160A
CC2 250A
CC2 400A
Thermal Magnetic Protection
Change from 3P to 4P for 160A
Change from 3P to 4P for 250A
Change from 3P to 4P for 400A
Extra to change to motorized circuit breaker 160A
Extra to change to motorized circuit breaker 250A
Extra to change to motorized circuit breaker 400A
Deepsea
Change of CEx for DSE7310
Change of CEx for DSE7320 controller

Power


kVA

120
 
132
Prime power  (109 - 1259)
Stand by  (120 - 1539)

kW

96
 
106
Prime power  (87 - 1007)
Stand by  (96 - 1232)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
290
Width (B)
90
High (C)
0
 

Weight


 
Weight
Weight with liquid in radiator and carter

1.314
 

Fuel capacity


 
 
250