HGE-215 T5 NG

 

HGE-215 T5 NG

215 kVA COP Generator set Open Skid

Powered by: TEDOM
Alternator: STAMFORD

 

Three phase | 50 Hz | Natural Gas |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Output: 186,7kW cop
  • Manufacturer: TEDOM
  • Model: TG 190 G5V TA 86
  • Engine Type: 4-stroke Otto Cycle
  • Injection Type: Carburization
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 6 - L
  • Bore and Stroke: 130 x 150 mm
  • Displacement: 11,946 L
  • Cooling System: Coolant
  • Lube Oil Specifications: SAE 15 W40
  • Compression Ratio: 12:1
  • Fuel Consumption 100% PRP: 50,9 Nm3/h
  • Fuel Consumption 75 % PRP: 38,6 Nm3/h
  • Fuel Consumption 50 % PRP: 27,6 Nm3/h
  • Fuel Consumption 25 % PRP: 16,7 Nm3/h
  • Lube oil consumption with full load: 0,5
  • Total oil capacity including tubes, filters 56 L
  • Total coolant capacity: 30,5 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Natural Gas engine
  • 4-stroke cycle
  • Water-cooled
  • 24V electrical system
  • Dry air filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Self-excited and self-regulated
  • AVR governor
  • IP23 protection
  • H class insulation
  • Single drive-shaft
  • Flexible disc coupling
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • 4-pole thermal magnetic circuit breaker
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Battery Switch (opcional)
  • Emergency stop button
  • Steel chassis
  • Oil sump extraction kit
  • Anti-vibration shock absorbers
  • Steel industrial silencer -15db(A) attenuation
  • Steel residential silencer -35db(A) attenuation. (opcional)
  • Manual shut-off valve
  • Gas filter
  • Double solenoid valve
  • Primary pressure regulator
  • Secondary pressure regulator (Zero pressure regulator)
  • Low pressure switch
  • Valve (tightness) testing system
  • Inlet pressure manometer
  • Outlet pressure manometer
  • Special Start/Stop sequence
  • High pressure regulator (opcional)
  • High pressure switch (opcional)
  • Generator
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-1 11"1/2
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - Electrical system.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • 4-pole thermal magnetic circuit breaker
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Battery Switch Optional
  • - Open set version.
  • Steel chassis
  • Oil sump extraction kit
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Steel industrial silencer -15db(A) attenuation
  • Steel residential silencer -35db(A) attenuation. Optional
  • - Gas ramp.
  • Manual shut-off valve
  • Gas filter
  • Double solenoid valve
  • Primary pressure regulator
  • Secondary pressure regulator (Zero pressure regulator)
  • Low pressure switch
  • Valve (tightness) testing system
  • Inlet pressure manometer
  • Outlet pressure manometer
  • Special Start/Stop sequence
  • High pressure regulator Optional
  • High pressure switch Optional
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 551 ºC
  • Maximum allowed back pressure: 4,5 kPa
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 844,1 m3/h
  • Alternator fan air flow: 0,58 m3/s
  • - STARTING SYSTEM.
  • Starting power: 6,6 kW
  • Starting power: 8,98 CV
  • Recommended battery: 150 Ah
  • Auxiliary Voltage: 24 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Natural Gas
  • - Dimensions.
  • Length: 3.310 mm
  • Height: 1.863 mm
  • Width: 1.390 mm
  • Maximum shipping volume: 8,57 m3
  • Weight with liquids in radiator and sump: 2.711 kg
Residential Silencer
Residential Silencer E240P320M405N420K435F440D510
Protections
Earth Leakage Protection to 630A
CEx Optionals
Telesignal
Kit CAN / LAN
Change over power source unit AC5 / CC2
Repetitive display: Remote Screen
Alarm Indicator Panel RAM7
Kit CAN/RS-485
Kit CAN/USB
Kit MODBUS TCP/IP
Kit CAN Profibus
Kit CAN/SNMP
Fleet Manager Module - C2CLOUD
C2CLOUD - 3G/GRPS and GPS
Kit CAN/LAN HG
Deepsea Optionals
DSE2133: RTD/THERMOCOUPLE Input Expansion Module
DSE2130:Input Expansion Module
DSE2157:Output Expansion Module
DSE2548:Led Output Expansion Module
DSE2152: Analog Outputs Module
DSE2131:Digital / Resistive inputs module
DSE890
Thermal Magnetic Protection
Change from 4P to 3P for 400A
Extra to change to motorized circuit breaker 400A
Deepsea
Change of CEx for DSE7310
Change of CEx for DSE7320 controller

Power


kVA

0
Stand by  (90 - 173)

kW

0
Stand by  (72 - 138)

COP

172
 
215
kW  (73 - 193)
kVA  (73 - 193)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
331
Width (B)
139
High (C)
186,30
 

Weight


 
Weight
Weight with liquid in radiator and carter

2.711
 

Fuel capacity