HGO-25 T5 NG

 

HGO-25 T5 NG

25 kVA Generator set Open Skid

Powered by: FORD
Alternator: MECC ALTE

 

Three phase | 50 Hz | Natural Gas |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Output: 22,6kW prp ; 24,8kW standby
  • Manufacturer: FORD
  • Model: MSG425
  • Engine Type: 4-stroke Otto Cycle
  • Injection Type: Carburization
  • Aspiration Type: Natural
  • Bore and Stroke: 89 x 100 mm
  • Displacement: 2,5 L
  • Cooling System: Coolant
  • Lube Oil Specifications: API SJ/SH, SAE 5W-20
  • Compression Ratio: 9,7:1
  • Fuel Consumption 100% PRP: 7,2 Nm3/h
  • Total oil capacity including tubes, filters 6,3 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Natural Gas engine
  • 4-stroke cycle
  • Water-cooled
  • 12V electrical system
  • Dry air filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • - GENERATOR.
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-4 10"
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Steel industrial silencer -15db(A) attenuation
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - GAS RAMP.
  • Gas filter
  • Double solenoid valve
  • High pressure regulator
  • Primary pressure regulator
  • Low pressure switch
  • Inlet pressure manometer
  • Outlet pressure manometer
  • Special Start/Stop sequence
  • High pressure switch (Optional)
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • 4-pole thermal magnetic circuit breaker
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Battery Switch (Optional)
  • - EXHAUST SYSTEM.
  • Exhaust Gas Flow: 4,9 m3/min
  • Maximum allowed back pressure: 20,32 kPa
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 297,3 m3/h
  • Cooling Air Flow: 1,2 m3/s
  • Alternator fan air flow: 0,088 m3/s
  • - STARTING SYSTEM.
  • Recommended battery: 95 Ah
  • Auxiliary Voltage: 12 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Natural Gas
  • - DIMENSIONS.
  • Length: 1.750 mm
  • Height: 1.487 mm
  • Width: 900 mm
  • Maximum shipping volume: 2,34 m3
  • Weight with liquids in radiator and sump: 570 kg
Protections
Earth Leakage Protection to 630A
CEx Optionals
Telesignal
Kit CAN / LAN
Change over power source unit AC5 / CC2
Repetitive display: Remote Screen
Alarm Indicator Panel RAM7
Kit CAN/RS-485
Kit MODBUS TCP/IP
Kit CAN Profibus
Kit CAN/SNMP
Fleet Manager Module - C2CLOUD
C2CLOUD - 3G/GRPS and GPS
Kit CAN/LAN HG
Deepsea Options
DSE2133: RTD/THERMOCOUPLE Input Expansion Module
DSE2130:Input Expansion Module
DSE2157:Output Expansion Module
DSE2548:Led Output Expansion Module
DSE2152: Analog Outputs Module
DSE2131:Digital / Resistive inputs module
DSE890
CC2
CC2 40A
CC2 50A
CC2 63A
CC2 100A
CC2 125A
CC2 160A
Deepsea
Change of CEx for DSE7310
Change of CEx for DSE7320 controller

Power


kVA

25
 
27
Prime power  (23 - 82)
Stand by  (25 - 90)

kW

19.8
 
21
Prime power  (18.4 - 66)
Stand by  (20 - 72)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
175
Width (B)
90
High (C)
148,70
 

Weight


 
Weight
Weight with liquid in radiator and carter

570
 

Fuel capacity